Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -2- HA026248
O
PERATION
Switch on the indicator. Following a 3 second self-test sequence,
you will see the display shown below. It is called the HOME
display.
A
LARM
I
NDICATION
The indicator has three internal ‘soft’ alarm setpoints which can be
attached to either the logic or relay outputs.
OP1 will flash when an alarm attached to the logic output becomes
true. (This is normally alarm 1). It will go steady when the alarm
is acknowledged but still true.
OP2 will flash when an alarm attached to the relay output becomes
true. (This is normally alarm 2 or 3). It will go steady when the
alarm is acknowledged but still true.
T
O ACKNOWLEDGE A NEW ALARM
Press and together. This will also reset any latched
alarms that are no longer true.
In addition to the OP beacons, alarm messages are flashed in the
main display. The tables below list all of the possible messages and
their meaning.
A
LARM
M
ESSAGES
Process Alarms
Message Meaning
Alarm 1 is active and it is a Low alarm.
Alarm 1 is active and it is a High alarm.
Alarm 2 is active and it is a Low alarm.
Alarm 2 is active and it is a High alarm.
Alarm 3 is active and it is a Low alarm.
Sensor Break:
Input sensor is open circuit or high
resistance. Check the sensor.
In addition to the above messages, the displayed process value will
flash if the input signal or the displayed value is out of range.
The table above shows normal process alarms. In the event of a
failure in the indicator or the sensor the following diagnostic alarm
messages are provided.
Diagnostic alarms
Message Meaning and (Action)
Electrically Erasable Memory Error:
A parameter value has been corrupted.
Contact Eurotherm Controls.
Hardware error
: (
Return for repair)
Low display range exceeded
: (Check input signal)
High display range exceeded:
(Check input signal)
Error 1: ROM self-test fail.
(Return for repair)
Error 2: RAM self-test fail.
(Return for repair)
Error 3: Watchdog fail
.
(Return for repair)
Error 4: Keyboard failure
. Stuck button, or a button
was pressed during power up.
Error 5: Input circuit failure.
(Return for repair)
Power failure.
The line voltage is too low.
T
O
V
IEW THE
D
ISPLAY
U
NITS
Press and release quickly the or button. The display units
will be flashed for 0.5sec
If you get lost, pressing
and together will return you to
the HOME display.
If, at any time, no key is pressed within 45 seconds, the display
will always return to the HOME display.
HOME D
ISPLAY
O
PTIONS
Quickly press twice
T
O
C
HANGE THE
A
LARM
S
ETPOINTS
(T
RIP
L
EVELS
)
The button steps through parameter list headings. The first list
is the alarm setpoints. The other lists are shown on the next page.
The process value (PV)*
* See HOME display options for
other possibilities
Output 1

OP1
OP2
Output 2

Display Units
Degrees Centigrade
Degrees Fahrenheit
Kelvin
Linear inputs - no units displayed

0.5 sec
or
Press
or
to select:
Not used by indicator
Not used by indicator. (Only
applies to software version 1.4)
The HOME display will be
blank and only alarm
messages will be flashed
The Process value will be
displayed
Alarm 2 setpoint will be
displayed and can be
adjusted by
or
The Process value will be
displayed with Alarm 2
setpoint viewed and
adjusted by
or
0;
O0
2 secs
Press to return to the
HOME display
or
Next list

0.5 sec
Pressing or displays
to indicate that this a list heading
2 secs
)O6
)
1st
press

BBB
There are three
alarm setpoints.
The first character
is the alarm
setpoint number,
the next three the
alarm type, as
follows:
Low alarm
High alarm
If an alarm has
been disabled, it
will not appear in
this list.
Press
or
to
change the setpoint.

BBB
Press
or
to
change the setpoint.

)
Press and together to return
to the HOME display.
Alarm 1
Alarm 2
Alarm 3
Press
or
to
change the setpoint.
P
ress
2nd
press
To prevent an Operator
changing this option, see
“To Hide Parameters” .
Vista de página 1