Installation and Operation Handbook Understanding the Ordering Code
2216e Controller A-3
Software code
Sensor input Range min Range max Units Logic input
1
Logic input
2
Options
K 0
(note 2)
1000
(note 2)
C XX XX CF
Sensor input Range Min Range Min
Standard sensors
Min
°
C max Min
°
F max
J J thermocouple -210 1200 -340 2192
K K thermocouple -200 1372 -325 2500
T T thermocouple -200 400 -325 750
L L thermocouple -200 900 -325 1650
N N thermocouple -200 1300 -325 2370
R R thermocouple -50 1768 -58 3200
S S thermocouple -50 1768 -58 3200
B B thermocouple 0 1820 32 3310
P Platinel II therm’ple 0 1369 32 2496
C *C thermocouple
W5%Re/W26%Re
(Hoskins)
0 2319 32 4200
Z RTD/PT100 -200 850 -325 1562
Custom sensors
(*replaces C thermocouple)
D W3%Re/W25%Re 0 2399 32 4350
E E thermocouple -200 1000 -325 1830
1 Ni/Ni18%Mo 0 1399 32 2550
2 Pt20%Rh/Pt40%R
h
0 1870 32 3398
3 W/W26%Re
(Englehard)
0 2000 32 3632
4 W/W26%Re
(Hoskins)
0 2010 32 3650
5 W5%Re/W26%Re
(Englehard)
10 2300 50 4172
6 W5%Re/W26%Re
(Bucose)
0 2000 32 3632
7 Pt10%Rh/Pt40%R
h
-200 1800 392 3272
Linear inputs Min Max
F -100 to +100mV -999 9999
Y 0 to 20mA -999 9999
A 4 to 20ma -999 9999
W 0 to 5Vdc -999 9999
G 1 to 5Vdc -999 9999
V 0 to 10Vdc -999 9999
Options
Add as many options as
required
Control options
DP Direct acting PID
Heating option
PD Power feedback
disabled
Cooling options
XX Linear cooling
CF Fan cooling
CW Water cooling
CL Oil cooling
Logic inputs 1 & 2
XX Disabled
AM Manual mode select
SR Remote setpoint select
S2 Second setpoint
EH Integral hold
AC Alarm acknowledge
SB Standby mode
Units
C Centigrade
F Fahrenheit
K Kelvin
X Blank